DC 2-Wire (PUR Cable/Self-diagnosis Output), AC 2-Wire and AC/DC 2-Wire
            
        
E2E-series DC 2-Wire and 3-Wire Models (2E-X[]D[], E2E-X[]E[], E2E-X[]F[]) have been integrated into the E2E NEXT Series. Refer to the catalog (Cat. No. D120) for details.
last update: October 11, 2022
| Size | M8 | M12 | ||
|---|---|---|---|---|
| Shielded | Shielded | Shielded | Unshielded | |
| Model | E2E-X2D[] | E2E-X3D[] | E2E-X8MD[] | |
| Sensing distance | 2 mm ±10% | 3 mm ±10% | 8 mm ±10% | |
| Set distance *1 | 0 to 1.6 mm | 0 to 2.4 mm | 0 to 6.4 mm | |
| Differential travel | 15% max. of sensing distance | 10% max. of sensing distance | ||
| Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
 Engineering Data on Data Sheet.)  | 
|||
| Standard sensing object | Iron,
 8 × 8 × 1 mm  | 
Iron,
 12 × 12 × 1 mm  | 
Iron,
 30 × 30 × 1 mm  | 
|
| Response frequency *2 | 1.5 kHz | 0.8 kHz | ||
| Power supply voltage
 (operating voltage range)  | 
12 to 24 VDC, ripple (p-p): 10% max. (10 to 30 VDC) | |||
| Leakage current | 0.8 mA max. | |||
| Control
 output  | 
Load current | 3 to 100 mA, Diagnostic output: 50 mA for -D1(5)S Models | ||
| Residual
 voltage  | 
3 V max. (Load current: 100 mA, Cable length: 2 m) | |||
| Indicators | D1 Models: Operation indicator (red) and setting indicator (green)
 D2 Models: Operation indicator (red)  | 
|||
| Operation mode
 (with sensing object approaching)  | 
D1 Models: NO
 D2 Models: NC Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.  | 
|||
| Diagnostic output delay | 0.3 to 1 s | |||
| Protection circuits | Surge suppressor, Load short-circuit protection (for control and diagnostic output) | |||
| Ambient temperature
 range  | 
Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | |||
| Ambient humidity range | Operating/storage: 35% to 95% (with no condensation) | |||
| Temperature influence | ±15% max. of sensing distance at 23°C
 in the temperature range of -25 to 70°C  | 
±10% max. of sensing distance at 23°C in
 the temperature range of -25 to 70°C  | 
||
| Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | |||
| Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | |||
| Dielectric strength | 1000 VAC, 50/60 Hz for 1 minute between current carry parts and case | |||
| Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
 directions  | 
|||
| Shock resistance | Destruction: 500 m/s2 10 times each in X,
 Y, and Z directions  | 
Destruction: 1,000 m/s2 10 times each in X,
 Y, and Z directions  | 
||
| Degree of protection | Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant
 Connector Models: IEC 60529 IP67  | 
|||
| Connection method | Pre-wired Models (Standard cable length: 2 m), Connector Models, or Pre-wired
 Connector Models (Standard cable length: 0.3 m)  | 
|||
| Weight
 (packed state)  | 
Pre-wired
 Models  | 
Approx. 60 g | Approx. 70 g | |
| Pre-wired
 Connector Models  | 
--- | Approx. 40 g
 (Shielded Models only)  | 
||
| Connector
 Models  | 
Approx. 15 g | Approx. 25 g | ||
| Materi-
 als  | 
Case | Stainless steel (SUS303) | Nickel-plated brass | |
| Sensing surface | PBT | |||
| Clamping nuts | Nickel-plated brass | |||
| Toothed washer | Zinc-plated iron | |||
| Accessories | Instruction manual | |||
| Size | M18 | M30 | |||
|---|---|---|---|---|---|
| Shielded | Shielded | Unshielded | Shielded | Unshielded | |
| Model | E2E-X7D[] | E2E-X14MD[] | E2E-X10D[] | E2E-X20MD[] | |
| Sensing distance | 7 mm ±10% | 14 mm ±10% | 10 mm ±10% | 20 mm ±10% | |
| Set distance *1 | 0 to 5.6 mm | 0 to 11.2 mm | 0 to 8 mm | 0 to 16 mm | |
| Differential travel | 10% max. of sensing distance | ||||
| Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
 Engineering Data on Data Sheet.)  | 
||||
| Standard sensing object | Iron,
 18 × 18 × 1 mm  | 
Iron, 30 × 30 × 1 mm | Iron,
 54 × 54 × 1 mm  | 
||
| Response frequency *2 | 0.5 kHz | 0.4 kHz | 0.1 kHz | ||
| Power supply voltage
 (operating voltage range)  | 
12 to 24 VDC, ripple (p-p): 10% max. (10 to 30 VDC) | ||||
| Leakage current | 0.8 mA max. | ||||
| Control
 output  | 
Load current | 3 to 100 mA, Diagnostic output: 50 mA for -D1(5)S Models | |||
| Residual
 voltage  | 
3 V max. (Load current: 100 mA, Cable length: 2 m) | ||||
| Indicators | D1 Models: Operation indicator (red) and setting indicator (green)
 D2 Models: Operation indicator (red)  | 
||||
| Operation mode
 (with sensing object approaching)  | 
D1 Models: NO
 D2 Models: NC Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.  | 
||||
| Diagnostic output delay | 0.3 to 1 s | ||||
| Protection circuits | Surge suppressor, Load short-circuit protection (for control and diagnostic output) | ||||
| Ambient temperature
 range  | 
Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | ||||
| Ambient humidity range | Operating/storage: 35% to 95% (with no condensation) | ||||
| Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | ||||
| Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
| Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
| Dielectric strength | 1000 VAC, 50/60 Hz for 1 minute between current carry parts and case | ||||
| Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
 directions  | 
||||
| Shock resistance | Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions | ||||
| Degree of protection | Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant
 Connector Models: IEC 60529 IP67  | 
||||
| Connection method | Pre-wired Models (Standard cable length: 2 m), Connector Models, or Pre-wired
 Connector Models (Standard cable length: 0.3 m)  | 
||||
| Weight
 (packed state)  | 
Pre-wired
 Models  | 
Approx. 130 g | Approx. 175 g | ||
| Pre-wired
 Connector Models  | 
--- | --- | |||
| Connector
 Models  | 
Approx. 40 g | Approx. 90 g | |||
| Materi-
 als  | 
Case | Nickel-plated brass | |||
| Sensing surface | PBT | ||||
| Clamping nuts | Nickel-plated brass | ||||
| Toothed washer | Zinc-plated iron | ||||
| Accessories | Instruction manual | ||||
            *1. Use the E2E within the range in which the setting indicator (green LED) is ON (except D2 Models).
*2. The response frequency is an average value.
       Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object,
       and a set distance of half the sensing distance.
        
| Size | M8 | M12 | |||
|---|---|---|---|---|---|
| Shielded | Shielded | Unshielded | Shielded | Unshielded | |
| Model | E2E-X1R5Y[] | E2E-X2MY[] | E2E-X2Y[] | E2E-X5MY[] | |
| Sensing distance | 1.5 mm ±10% | 2 mm ±10% | 5 mm ±10% | ||
| Set distance | 0 to 1.2 mm | 0 to 1.6 mm | 0 to 4 mm | ||
| Differential travel | 10% max. of sensing distance | ||||
| Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
 Engineering Data on Data Sheet.)  | 
||||
| Standard sensing object | Iron,
 8 × 8 × 1 mm  | 
Iron, 12 × 12 × 1 mm | Iron,
 15 × 15 × 1 mm  | 
||
| Response frequency | 25 Hz | ||||
| Power supply voltage
 (operating voltage range) *1  | 
24 to 240 VAC (20 to 264 VAC), 50/60 Hz | ||||
| Leakage current | 1.7 mA max. | ||||
| Control
 output  | 
Load current *2 | 5 to 100 mA | 5 to 200 mA | ||
| Residual voltage | Refer to Engineering Data on Data Sheet. | ||||
| Indicators | Operation indicator (red) | ||||
| Operation mode
 (with sensing object approaching)  | 
Y1 Models: NO
 Y2 Models: NC Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.  | 
||||
| Protection circuits | Surge suppressor | ||||
| Ambient temperature range
 *1 *2  | 
Operating/Storage: -25 to 70°C
 (with no icing or condensation)  | 
Operating/Storage: -40 to 85°C
 (with no icing or condensation)  | 
|||
| Ambient humidity range | Operating/storage: 35% to 95% (with no condensation) | ||||
| Temperature influence | ±10% max. of sensing distance at 23°C
 in the temperature range of -25 to 70°C  | 
±15% max. of sensing distance at 23°C
 in the temperature range of -40 to 85°C, ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C  | 
|||
| Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
| Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
| Dielectric strength | 4,000 VAC (M8 Models: 2,000 VAC), 50/60 Hz for 1 min between current-carrying
 parts and case  | 
||||
| Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
 directions  | 
||||
| Shock resistance | Destruction: 500 m/s2 10 times each in
 X, Y, and Z directions  | 
Destruction: 1,000 m/s2 10 times each
 in X, Y, and Z directions  | 
|||
| Degree of protection | Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant
 Connector Models: IEC 60529 IP67  | 
||||
| Connection method | Pre-wired Models (Standard cable length: 2 m) and Connector Models | ||||
| Weight
 (packed state)  | 
Pre-wired Models
 Model  | 
Approx. 60 g | Approx. 70 g | ||
| Connector Models | Approx. 15 g | Approx. 25 g | |||
| Materials | Case | Stainless steel (SUS303) | Nickel-plated brass | ||
| Sensing surface | PBT | ||||
| Clamping nuts | Nickel-plated brass | ||||
| Toothed washer | Zinc-plated iron | ||||
| Accessories | Instruction manual | ||||
| Size | M18 | M30 | |||
|---|---|---|---|---|---|
| Shielded | Shielded | Unshielded | Shielded | Unshielded | |
| Model | E2E-X5Y[] | E2E-X10MY[] | E2E-X10Y[] | E2E-X18MY[] | |
| Sensing distance | 5 mm ±10% | 10 mm ±10% | 18 mm ±10% | ||
| Set distance | 0 to 4 mm | 0 to 8 mm | 0 to 14 mm | ||
| Differential travel | 10% max. of sensing distance | ||||
| Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
 Engineering Data on Data Sheet.)  | 
||||
| Standard sensing object | Iron,
 18 × 18 × 1 mm  | 
Iron, 30 × 30 × 1 mm | Iron,
 54 × 54 × 1 mm  | 
||
| Response frequency | 25 Hz | ||||
| Power supply voltage
 (operating voltage range) *1  | 
24 to 240 VAC (20 to 264 VAC), 50/60 Hz | ||||
| Leakage current | 1.7 mA max. | ||||
| Control
 output  | 
Load current *2 | 5 to 300 mA | |||
| Residual voltage | Refer to Engineering Data on Data Sheet. | ||||
| Indicators | Operation indicator (red) | ||||
| Operation mode
 (with sensing object approaching)  | 
Y1 Models: NO
 Y2 Models: NC Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.  | 
||||
| Protection circuits | Surge suppressor | ||||
| Ambient temperature range
 *1 *2  | 
Operating/Storage: -40 to 85°C (with no icing or condensation) | ||||
| Ambient humidity range | Operating/storage: 35% to 95% (with no condensation) | ||||
| Temperature influence | ±15% max. of sensing distance at 23°C in the temperature range of -40 to 85°C,
 ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C  | 
||||
| Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
| Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
| Dielectric strength | 4,000 VAC (M8 Models: 2,000 VAC), 50/60 Hz for 1 min between current-carrying
 parts and case  | 
||||
| Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
 directions  | 
||||
| Shock resistance | Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions | ||||
| Degree of protection | Pre-wired Models: IEC 60529 IP67, in-house standards: oil-resistant
 Connector Models: IEC 60529 IP67  | 
||||
| Connection method | Pre-wired Models (Standard cable length: 2 m) and Connector Models | ||||
| Weight
 (packed state)  | 
Pre-wired Models
 Model  | 
Approx. 130 g | Approx. 175 g | ||
| Connector Models | Approx. 40 g | Approx. 90 g | |||
| Materials | Case | Stainless steel (SUS303) | Nickel-plated brass | ||
| Sensing surface | PBT | ||||
| Clamping nuts | Nickel-plated brass | ||||
| Toothed washer | Zinc-plated iron | ||||
| Accessories | Instruction manual | ||||
            *1. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is at
       least −25°C.
*2. When using an M18 or M30 Connector Model at an ambient temperature between 70 and 85°C, make sure that the
       Sensor has a control output (load current) of 5 to 200 mA max.
        
| Size | M12 | M18 | M30 | |
|---|---|---|---|---|
| Shielded | Shielded | |||
| Model | E2E-X3T1 | E2E-X7T1 | E2E-X10T1 | |
| Sensing distance | 3 mm ±10% | 7 mm ±10% | 10 mm ±10% | |
| Set distance | 0 to 2.4 mm | 0 to 5.6 mm | 0 to 8 mm | |
| Differential travel | 10% max. of sensing distance | |||
| Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
 Engineering Data on Data Sheet.)  | 
									|||
| Standard sensing object | Iron, 12 × 12 × 1 mm | Iron, 18 × 18 × 1 mm | Iron, 30 × 30 × 1 mm | |
| Response
 frequency *1  | 
										DC | 1 kHz | 0.5 kHz | 0.4 kHz | 
| AC | 25 Hz | |||
| Power supply voltage
 (operating voltage range) *2  | 
										24 to 240 VDC (20 to 264 VDC)
 48 to 240 VAC (40 to 264 VAC)  | 
									|||
| Leakage current | DC: 1 mA max.
 AC: 2 mA max.  | 
									|||
| Control
 output  | 
										Load current | 5 to 100 mA | ||
| Residual
 voltage  | 
										DC: 6 V max. (Load current: 100 mA, Cable length: 2 m)
 AC: 10 V max. (Load current: 5 mA, Cable length: 2 m)  | 
									|||
| Indicators | Operation indicator (red), Setting indicator (green) | |||
| Operation mode
 (with sensing object approaching)  | 
										NO (Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.) | |||
| Protection circuits | Load short-circuit protection (20 to 40 VDC only), Surge suppressor | |||
| Ambient temperature range | Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | |||
| Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | |||
| Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | |||
| Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | |||
| Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | |||
| Dielectric strength | 4,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | |||
| Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z
 directions  | 
									|||
| Shock resistance | Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions | |||
| Degree of protection | IEC 60529 IP67, in-house standards: oil-resistant | |||
| Connection method | Pre-wired Models (Standard cable length: 2 m) | |||
| Weight (packed state) | Approx. 80 g | Approx. 140 g | Approx. 190 g | |
| Materials | Case | Nickel-plated brass | ||
| Sensing surface | PBT | |||
| Clamping nuts | Nickel-plated brass | |||
| Toothed washer | Zinc-plated iron | |||
| Accessories | Instruction manual | |||
            *1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a
       distance of twice the standard sensing object, and a set distance of half the sensing distance.
*2. Power Supply Voltage Waveform:
       Use a sine wave for the power supply. Using a rectangular AC power supply may result in faulty reset.
        
last update: October 11, 2022