| Item | Specifications | |
|---|---|---|
| Enclosure | Mounted in a panel | |
| Grounding Methods | Ground to less than 100 Ω | |
| Operating environment | Ambient operating temperature | 0 to 55°C | 
| Ambient operating humidity | 10 to 95% (with no condensation or icing) | |
| Atmosphere | Must be free from corrosive gases. | |
| Ambient storage temperature | -25 to 70°C (with no condensation or icing) | |
| Altitude | 2,000 m max. | |
| Pollution degree | 2 or less: Conforms to JIS B3502 and IEC 61131-2 | |
| Noise immunity | 2 kV on power supply line (Conforms to IEC61000-4-4.) | |
| Overvoltage category | Category II: Conforms to JIS B3502 and IEC 61131-2 | |
| EMC immunity level | Zone B | |
| Vibration resistance | Conforms to IEC 60068-2-6. 5 to 8.4 Hz with amplitude of 3.5 mm, 8.4 to 150 Hz, acceleration of 9.8 m/s2 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) | |
| Shock resistance | Conforms to IEC 60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions | |
| Applicable standards | cULus: Listed (UL61010-2-201), ANSI/ISA12.12.01, EU: EN61131-2, RCM, KC: KC Registration | |
This section describes the functions provided in an RFID Unit.
| Function name | Description | 
|---|---|
| RF Communications option function | This function switches the operation sequence during communications with an RF Tag. | 
| Communications command function | This function reads or writes the memory for a RF Tag on the antenna communications area. | 
| Write protection function | This function prevents the loss of data due to overwriting by specifying the areas in which it is not possible to write to an RF Tag. | 
| RF Tag service life detection function | This function records the number of times data is rewritten to an RF Tag, and determines the maximum rewrite count. | 
| RF Tag memory error detection function | This function detects an error during reading by performing CRC calculation for the memory of an RF Tag. | 
| RF Tag memory error correction function | This function detects an error during reading by performing ECC calculation for the memory of an RF Tag, and corrects the error to an appropriate value. | 
| Test command function | This function checks the margin in communications with an RF Tag, and measures the surrounding noise. | 
| Unit name | One-channel RFID Unit | Model | NX-V680C1 | 
|---|---|---|---|
| Number of antennas connected | 1 | External connection terminal | FG terminal block (1 terminal) | 
| I/O refreshing method | Free-Run Refreshing | ||
| Indicators | TS indicator, RF indicator, NORM indicator, and ERR indicator  | Communications protocol | ISO/IEC18000-3 (15693) | 
| Connectable Antennas | V680-series Antenna with Separate Amplifier: V680-HS[][] Antenna with Built-in Amplifier: V680-H01-V2 | ||
| Applicable RF Tags | V680S-series RF or V680-series RF Tags | ||
| RF Tag reading/ writing size | 8,192 bytes max. | ||
| Divided data size | 16 to 128 bytes | ||
| Backup function | Supported. | ||
| Dimensions | 30 mm (W) x 100 mm (H) x 71 mm (D) | Isolation method | Digital isolator isolation | 
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute with a leakage current of 5 mA max. | 
| I/O power supply method | Supplied from the NX bus | Current consumption from I/O power supply | • V680-H01-V2 connection 250 mA max. • V680-HA63[] connection 210 mA max. | 
| NX Unit power consumption | • Connected to a CPU Unit 1.00 W max. • Connected to Communications Coupler Unit 0.90 W max. | Weight | 120 g max. | 
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit Possible in upright installation. • Connected to a Communications Coupler Unit Possible in 6 orientations Restrictions: No restrictions | ||
| Unit name | Two-channels RFID Unit | Model | NX-V680C2 | 
|---|---|---|---|
| Number of antennas connected | 2 | External connection terminal | FG terminal block (1 terminal) | 
| I/O refreshing method | Free-Run Refreshing | ||
| Indicators | [TS] LED, [RF] LED, [NORM] LED, [ERR] LED TS indicator, RF indicator, NORM indicator, and ERR indicator  | Communications protocol | ISO/IEC18000-3 (15693) | 
| Connectable Antennas | V680-series Antenna with Separate Amplifier: V680-HS[][] | ||
| Applicable RF Tags | V680S-series RF or V680-series RF Tags | ||
| RF Tag reading/ writing size | 8,192 bytes max. | ||
| Divided data size | 16 to 128 bytes | ||
| Backup function | Supported. | ||
| Dimensions | 30 mm (W) x 100 mm (H) x 71 mm (D) | Isolation method | Digital isolator isolation | 
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute with a leakage current of 5 mA max. | 
| I/O power supply method | Supplied from the NX bus. | Current consumption from I/O power supply | V680-HA63[] connection 380 mA max | 
| NX Unit power consumption | • Connected to a CPU Unit 1.00 W max. • Connected to Communications Coupler Unit 0.90 W max. | Weight | 130 g max. | 
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit Possible in upright installation. • Connected to a Communications Coupler Unit Possible in 6 orientations Restrictions: No restrictions | ||
Refer to the user's manual for the CPU Unit for the models of CPU Unit to which RFID Units can be connected.
| NX Units | Corresponding unit versions/versions | ||
|---|---|---|---|
| Model | Units Versions | CPU Units | Sysmac Studio | 
| NX-V680C1 | Ver. 1.0 | Version 1.13 or higher | Version 1.25 or higher | 
| NX-V680C2 | |||
| NX Unit | Corresponding unit versions/versions | |||
|---|---|---|---|---|
| Model | Unit Version | EtherCAT Couplers Units | CPU Unit or Industrial PC | Sysmac Studio | 
| NX-V680C1 | Ver. 1.0 | 1.0 or later * | 1.05 or higher | Version 1.25 or higher | 
| NX-V680C2 | ||||
* When connecting with other manufacturer's master, use the EtherCAT Coupler Unit with unit version Ver.1.5 or later.
| NX Unit | Corresponding unit versions/versions | ||||||
|---|---|---|---|---|---|---|---|
| Model | Unit Version | Use with an NJ/NX/NY-series Controller *1 | Use with an CS/CJ/CP-series PLC *2 | ||||
| EtherNet/IP Coupler Unit | CPU Unit or Industrial PC | Sysmac Studio | EtherNet/IP Coupler Unit | Sysmac Studio | NX-IO Configurator | ||
| NX-V680C1 | Ver. 1.0 | Version 1.2 or later | Version 1.14 or later | Version 1.25 or higher | Version 1.2 or later | Version 1.25 or higher | Version 1.13 or later | 
| NX-V680C2 | |||||||