Page top

Industrial Automation

Industrial Automation

PYF-[][]-PU / PTF-[][]-PU / P2RF-[][]-PU

Sockets with Push-In Plus technology

PYF-[][]-PU / PTF-[][]-PU / P2RF-[][]-PU

Our Value Design Products Increase the Value of Your Control Panels. Sockets with Push-In Plus technology to Save Work Added to Series for MY, LY and G2R-S Relays.

Characteristics

Sockets

PYF-[][]-PU(-L)

Item PYF-08-PU (-L) PYF-14-PU (-L)
Ambient operating temperature -40 to 70°C
Ambient operating humidity 5 to 85%
Rated carry current * 10 A 6 A
Dielectric
strength
Between contact terminals of same polarity 2,000 VAC, 1 min 2,000 VAC, 1 min
Between contact terminals of different polarity 2,000 VAC, 1 min 2,000 VAC, 1 min
Between coil and contact terminals 2,000 VAC, 1 min 2,000 VAC, 1 min
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Weight (approx.) 80 g 87 g

* The continuous carry current of 10 A for PYF-08-PU(-L) is for an ambient temperature of 55°C. At an ambient
   temperature of 70°C, the value is 7 A.

P2RF-[][]-PU

Item P2RF-05-PU P2RF-08-PU
Ambient operating temperature -40 to 70°C
Ambient operating humidity 5 to 85%
Rated carry current * 10 A 6 A
Dielectric
strength
Between contact terminals of same polarity 1,000 VAC, 1 min 1,000 VAC, 1 min
Between contact terminals of different polarity --- 3,000 VAC, 1 min
Between coil and contact terminals 4,000 VAC, 1 min 4,000 VAC, 1 min
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Weight (approx.) 40 g 45 g

* The continuous carry current of 10 A for P2RF-05-PU is for an ambient temperature of 55°C.
 At an ambient temperature of 70°C, the value is 7 A.
 The continuous carry current of 6 A for P2RF-08-PU is for an ambient temperature of 55°C.
 At an ambient temperature of 70°C, the value is 5 A.

PTF-[][]-PU(-L)

Item PTF-08-PU (-L) PTF-14-PU-L
Ambient operating temperature -40 to 70°C
Ambient operating humidity 5 to 85%
Rated carry current * 10 A
Dielectric
strength
Between contact terminals of same polarity 2,000 VAC, 1 min 2,000 VAC, 1 min
Between contact terminals of different polarity 2,000 VAC, 1 min 2,000 VAC, 1 min
Between coil and contact terminals 2,000 VAC, 1 min 2,000 VAC, 1 min
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Weight (approx.) 65 g 100 g

* The continuous carry current of 10 A for PTF-08-PU(-L) is for an ambient temperature of 55°C.
 At an ambient temperature of 70°C, the value is 7 A.
 The continuous carry current of 10 A for PTF-14-PU-L is for an ambient temperature of 40°C.
 At an ambient temperature of 70°C, the value is 7 A.

Accessories (Order Separately)

Short Bars

Application Applicable
sockets
Model Maximum
carry current
Ambient
operating
temperature
Ambient
operating
humidity
For Contact terminals
(common)
PYF-08-PU(-L)
PYF-14-PU(-L)
P2RF-05-PU
P2RF-08-PU
PYDN-7.75-020[] 20 A -40 to 70°C 5 to 85% Rh
PYDN-7.75-030[]
PYDN-7.75-040[]
PYDN-7.75-200[]
For Coil terminals P2RF-05-PU
P2RF-08-PU
PYDN-15.5-080[] 20 A -40 to 70°C 5 to 85% Rh
PYF-08-PU(-L)
PYF-14-PU(-L)
PYDN-31.0-080[]

Approved Standards

CSA certification (File No. LR031928)

Model Ratings Class No. Standard No.
PYF-08-PU (-L)
PTF-08-PU (-L)
P2RF-05-PU
10 A 250 V 3211 07 CSA C22.2 No14
PYF-14-PU (-L) 6A 250V *
PTF-14-PU (-L) 10 A 250 V
(Same polarity)
P2RF-08-PU 6 A 250 V

* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.

UL standard certification (File No. E87929)

Model Ratings Standard No. Category Listed/Recognized
PYF-08-PU (-L)
PTF-08-PU (-L)
P2RF-05-PU
10 A 250 V UL508 SWIV2 Recognized
PYF-14-PU (-L) 6 A 250 V *
PTF-14-PU (-L) 10 A 250 V
(Same polarity)
P2RF-08-PU 6 A 250 V

* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.

TÜV Rheinland certification

Model Ratings Standard No. Certification No.
PYF-08-PU (-L) 10 A 250 V *1 EN 61984 R50327595
PYF-14-PU (-L) 6 A 250 V
P2RF-05-PU 10 A 250 V *1 R50327599
P2RF-08-PU 6 A 250 V *3
PTF-08-PU (-L) 10 A 250 V *1 R50440885
PTF-14-PU (-L) 10 A 250 V *2

*1. Ratings are for an ambient temperature of 55°C. At an ambient temperature of 70°C, the value is 7 A.
*2. Ratings are for an ambient temperature of 40°C. At an ambient temperature of 70°C, the value is 7 A.
*3. Ratings are for an ambient temperature of 55°C. At an ambient temperature of 70°C, the value is 5 A.