CJ-series Process Analog I/O Unit
last update: September 24, 2012
Unit classification: CJ1 Special I/O Units
Input points: 4 inputs
Signal range selection: Set separately for each input
External connection: Removable terminal block
No. of unit numbers allocated: 1
Product
name |
Signal range | Conversion
speed (resolution) |
Accuracy
(at ambient temperature of 25 °C) |
Current
consump- tion (A) |
Model | Stand-
ards |
|
---|---|---|---|---|---|---|---|
5 V | 24 V | ||||||
Process
Input Units (Isolated- type Units with Universal Inputs) |
Fully universal inputs:
Pt100, JPt100, Pt1000, K, J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V |
Conversion
speed: 250 ms/ 4 inputs |
Accuracy:
Platinum resistance thermometer input: (± 0.3% of PV or ±0.8 °C, whichever is larger) ± 1 digit max. Thermocouple input: (±0.3% of PV or ±1.5°C, whichever is larger) ± 1digit max. *1 Voltage or current input: ±0.3% of F.S. ±1 digit max. |
0.32 | --- | CJ1W-AD04U | UC1,
CE, L |
Universal inputs:
Pt100 (3-wire), JPt100 (3-wire), Pt1000 (3-wire), Pt100 (4-wire), K, J, T, E, L, U, N, R, S, B, WRe5-26, PL II, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 1.25 V, 0 to 5 V, 0 to 10 V, ±100 mV selectable range -1.25 to 1.25 V, -5 to 5 V, -10 to 10 V, ±10 V selectable range, potentiometer |
Resolution
(conversion speed): 1/256,000 (conversion cycle: 60 ms/ 4 inputs) 1/64,000 (conversion cycle: 10 ms/ 4 inputs) 1/16,000 (conversion cycle: 5 ms/ 4 inputs) |
Standard accuracy:
±0.05% of F.S. |
0.3 | --- | CJ1W-PH41U
*2 |
UC1,
CE |
last update: September 24, 2012