SRM1-C01 / C02-V2

Master Control Units (S-Controllers)

SRM1-C01 / C02-V2

Subminiature, Stand-alone Model with CompoBus/S Master and SYSMAC Controller Functions

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Master Specifications

Number of I/O points 256 points (128 inputs/128 outputs)
128 points (64 inputs/64 outputs)
Selectable by DM setting. The default setting is 256 points.
Max. number of Slaves
per Master
256 points: 32
128 points: 16
I/O words Input words: 000 to 007
Output words: 010 to 017
Programming language Ladder diagram
Types of instruction 14 basic and 81 special instructions (125 instructions in total)
Execution time LD instruction: 0.97 μs
MOV instruction: 9.1 μs
Program capacity 4,096 words
Data memory 2,022 + 512 (read-only) words
Timers/Counters 128 timers/counters
Work bits 640 bits
Memory backup Flash memory (without battery): User programs
Lithium battery: Data memory etc. (Battery life: 10 years min. at an ambient temperature of
25°C.)
Peripheral port 1 point
RS-232C port 1 point (SRM1-C02 only)
Host Link, NT Link, 1:1 Link, or no protocol
Programming tool Programming Consoles: CQM1-PRO01-E, C200H-PRO27-E
CX-Programmer (Supported for versions 2 or later.)
WS02-CXP1-E
SYSMAC Support Software (MS-DOS version): C500-ZL3AT1-E

Communications Specifications

Communications method CompoBus/S protocol
Coding method Manchester coding method
Connection method Multi-drop method and T-branch method *1
Communications baud rate 750,000 bps/93,750 bps *2
Commu-
nications
cycle
time
High-speed
communications mode
0.5 ms with 8 Slaves for inputs and 8 Slaves for outputs
0.8 ms with 16 Slaves for inputs and 16 Slaves for outputs
Long-distance
communications mode
4.0 ms with 8 Slaves for inputs and 8 Slaves for outputs
6.0 ms with 16 Slaves for inputs and 16 Slaves for outputs
Communications cable 2-conductor VCTF cable (0.75 x 2), 4-conductor VCTF cable (0.75 x 4)
Dedicated flat cable
Commu-
nications
distance
High-speed
communications mode
2-conductor VCTF cable:
Main line length: 100 m max.
Branch line length: 3 m max.
Total branch line length: 50 m max.
Flat cable, 4-conductor VCTF cable:
Main line length: 30 m max.
Branch line length: 3 m max.
Total branch line length: 30 m max.
(When flat cable is used to connect fewer than 16 Slaves, the main line can be
up to 100 m long and the total branch line length can be up to 50 m.)
Long-distance
communications mode
2-conductor VCTF cable:
Main line length: 500 m max.
Branch line length: 6 m max.
Total branch line length: 120 m max.
Flat cable, 4-conductor VCTF cable:
Variable branch wiring (total cable length 200 m max.)
(There are no limits on the branching format or main, branch, or total line
lengths. The terminator must be connected to the point in the system farthest
from the master.)
Max. number of connecting nodes 32
Error control checks Manchester code check, frame length check, and parity check

*1. A terminator must be connected to the point in the system farthest from the Master.
*2. The communications baud rate is switched using DM settings (default setting is 750,000 bps).

General Specifications

Supply voltage 24 VDC
Allowable supply voltage 20.4 to 26.4 VDC
Power consumption 3.5 W max.
Inrush current 12.0 A max.
Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines)
Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z
directions for 80 minutes each
(Time coefficient; 8 minutes × coefficient factor 10 = total time 80 minutes)
Shock resistance 147 m/s2 three times each in X, Y, and Z directions
Ambient temperature Operating: 0°C to 55°C
Storage: -20°C to 75°C
Humidity 10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gas.
Terminal screw size M3
Power interrupt time DC type: 2 ms min.
Weight 150 g max.