Solid State Relays with Failure Detection Function
last update: January 5, 2022
Rated power supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 75 to 264 VAC (50/60 Hz) |
Current consumption | 15 mA AC max. (at 200 VAC) |
Input method | Voltage input |
---|---|
Rated input voltage | 12 to 24 VDC |
Operating input voltage range | 9.6 to 30 VDC |
Must operate voltage | 9.6 VDC max. |
Must release voltage | 1 VDC min. |
Input current | 7 mA DC max. (at rated input voltage) |
Rated load voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 75 to 264 VDC (50/60 Hz) |
Applicable load current | 20 A (Ta = 40) |
Minimum load current | 0.1 A |
Inrush current resistance (peak value) | 220 A (60 Hz, 1 cycle) |
Permissible (I2t) | 260 A2s |
Applicable load
(with Class-1 AC resistive load) |
4 kW (at 200 VAC) |
Output OFF collector voltage | 30 VDC max. |
---|---|
Maximum carry current | 0.1 A |
Output form | Independent NPN open collector |
Operate time | 1/2 of load power source cycle + 1 ms max. | |
---|---|---|
Release time | 1/2 of load power source cycle + 1 ms max. | |
Main circuit | Output ON voltage drop | 1.6 V rms max. |
OFF leakage current | 10 mA max. (at 200 VAC) | |
Alarm output | Output ON voltage drop | 1.5 V max. |
OFF leakage current | 0.1 mA max. | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |
Vibration resistance | Destruction: 10 to 55 to10 Hz, 0.35-mm single amplitude | |
Shock resistance | Destruction: 294 m/s2 | |
Ambient temperature | Operating: -20 to 60°C (with no icing or condensation)
Storage: -30 to 70°C (with no icing or condensation) |
|
Ambient humidity | 45% to 85% | |
Weight | Approx. 300 g | |
Certified standards | UL (File No.E64562), CSA (File No.LR35535), VDE (Certificate No.133114,
EN60947-4-3) |
|
EMC | Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2 |
last update: January 5, 2022