CP-series CP1E CPU Units
            
        
last update: February 1, 2023
| Type | AC power supply models | DC power supply models | |
|---|---|---|---|
| Model | CP1E-[][][]S[]D[]-A
 CP1E-[][][]D[]-A  | 
CP1E-[][][]S[]D[]-D
 CP1E-[][][]D[]-D  | 
|
| Enclosure | Mounted in a panel | ||
| Dimensions (H × D × W) | E/N/NA[][]-type
 CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 90mm *1 × 85mm *2 × 66 mm CPU Unit with 14 or 20 I/O points (CP1E-[]14D[]-[]/[]20D[]-[]): 90mm *1 × 85mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 90mm *1 × 85mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 90mm *1 × 85mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 90mm *1 × 85mm *2 × 195 mm CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 90mm *1 × 85mm *2 × 130 mm E/N/[][]S(1)-type CPU Unit with 14 or 20 I/O points (CP1E-[]14SD[]-[]/[]20SD[]-[]): 90mm *1 × 79mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-[]30S(1)D[]-[]): 90mm *1 × 79mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-[]40S(1)D[]-[]): 90mm *1 × 79mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-[]60S(1)D[]-[]): 90mm *1 × 79mm *2 × 195 mm  | 
||
| Weight | CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 300g max.
 CPU Unit with 14 I/O points (CP1E-[]14(S)D[]-[]): 360g max. CPU Unit with 20 I/O points (CP1E-[]20(S)D[]-[]): 370g max. CPU Unit with 30 I/O points (CP1E-[]30(S[])D[]-[]): 600g max. CPU Unit with 40 I/O points (CP1E-[]40(S[])D[]-[]): 660g max. CPU Unit with 60 I/O points (CP1E-[]60(S[])D[]-[]): 850g max. CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 680g max.  | 
||
| Elec-
 trical spec- ifica- tions  | 
Supply voltage | 100 to 240 VAC 50/60 Hz | 24 VDC | 
| Operating voltage
 range  | 
85 to 264 VAC | 20.4 to 26.4 VDC | |
| Power
 consumption  | 
15 VA/100 VAC max.
 25 VA/240 VAC max. (CP1E-E10D[]-A/[]14(S)D[]-A/ []20(S)D[]-A)  | 
9 W max. (CP1E-E10D[]-D)
 13 W max. (CP1E-N14D[]-D/N20D[]-D)  | 
|
| 50 VA/100 VAC max.
 70 VA/240 VAC max. (CP1E-NA20D[]-A/[]30(S[])D[]-A/ []40(S[])D[]-A/N60(S[])D[]-A)  | 
20 W max.
 (CP1E-NA20D[]-D/N30(S[])D[]-D/ N40(S[])D[]-D/N60(S[])D[]-D) *4  | 
||
| Inrush current | 120 VAC, 20 A for 8 ms max. for cold start
 at room temperature 240 VAC, 40 A for 8 ms max. for cold start at room temperature  | 
24 VDC, 30 A for 20 ms max. for cold start
 at room temperature  | 
|
| External power
 supply *3  | 
Not provided.
 (CP1E-E10D[]-A/[]14(S)D[]-A/ []20(S)D[]-A) 24 VDC, 300 mA (CP1E-NA20D[]-A/[]30D[]-A/ []40D[]-A/[]60D[]-A/[]30SDR-A/ []40SDR-A/[]60SDR-A)  | 
Not provided | |
| Insulation
 resistance  | 
20 MΩ min. (at 500 VDC) between the
 external AC terminals and GR terminals  | 
Except between DC primary current and DC
 secondary current  | 
|
| Dielectric
 strength  | 
2,300 VAC 50/60Hz for 1 min between AC
 external and GR terminals Leakage current: 5 mA max.  | 
Except between DC primary current and DC
 secondary current  | 
|
| Power OFF
 detection time  | 
10 ms min. | 2 ms min. | |
| Appli-
 cation envi- ron- ment  | 
Ambient operating
 temperature  | 
0 to 55 °C | |
| Ambient humidity | 10% to 90% | ||
| Atmosphere | No corrosive gas. | ||
| Ambient storage
 temperature  | 
-20 to 75 °C (excluding battery) | ||
| Altitude | 2,000 m max. | ||
| Pollution degree | 2 or less: Meets IEC 61010-2-201. | ||
| Noise resistance | 2 kV on power supply line (Conforms to IEC61000-4-4.) | ||
| Overvoltage
 category  | 
Category II: Meets IEC 61010-2-201. | ||
| EMC Immunity
 Level  | 
Zone B | ||
| Vibration
 resistance  | 
Conforms to JIS 60068-2-6.
 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)  | 
||
| Shock resistance | Conforms to JIS 60068-2-27.
 147 m/s2, 3 times in X, Y, and Z directions  | 
||
| Terminal block | Fixed (not removable) | ||
| Terminal screw size | M3 | ||
| Applicable standards | Conforms to EC Directive | ||
| Grounding method | Ground to 100 Ω or less. | ||
| Item | CP1E-E[][]SD[]-[]
 CP1E-[][]D[]-[]  | 
CP1E-N[][]S[]D[]-[]
 CP1E-N[][]D[]-[] CP1E-NA[][]D[]-[]  | 
||
|---|---|---|---|---|
| Program capacity | 2 K steps (8 Kbytes) including
 the symbol table, comments, and program indices of the CX-Programmer  | 
8 K steps (32 Kbytes) including the symbol
 table, comments, and program indices of the CX-Programmer  | 
||
| Control method | Stored program method | |||
| I/O control method | Cyclic scan with immediate refreshing | |||
| Program language | Ladder diagram | |||
| Instructions | Approximately 200 | |||
| Proc-
 essing speed  | 
Overhead processing time | 0.4 ms | ||
| Instruction execution times | Basic instructions (LD): 1.19 μs min.
 Special instructions (MOV): 7.9 μs min.  | 
|||
| Number of CP1W-series Expansion
 Units connected  | 
CP1E-E10D[]-[]/[]14(S)D[]-[]/[]20(S)D[]-[]: None
 CP1E-[]30(S[])D[]-[]/[]40(S[])D[]-[]/[]60(S[])D[]-[]/NA20(S[])D[]-[]: 3 units  | 
|||
| Maximum number of I/O points | CP1E-E10D[]-[]: 10
 CP1E-[]14(S)D[]-[]: 14 CP1E-[]20(S)D[]-[]: 20 CP1E-[]30(S[])D[]-[]: 150 (30 built in, 40 × 3 expansion) CP1E-[]40(S[])D[]-[]: 160 (40 built in, 40 × 3 expansion) CP1E-[]60(S[])D[]-[]: 180 (60 built in, 40 × 3 expansion) CP1E-NA20D[]-[]: 140 (20 built in, 40 × 3 expansion)  | 
|||
| Built-in I/O | CP1E-E10D[]-[]: 10 (6 inputs, 4 outputs)
 CP1E-[]14(S)D[]-[]: 14 (8 inputs, 6 outputs) CP1E-[]20(S)D[]-[]: 20 (12 inputs, 8 outputs) CP1E-[]30(S[])D[]-[]: 30 (18 inputs, 12 outputs) CP1E-[]40(S[])D[]-[]: 40 (24 inputs, 16 outputs) CP1E-[]60(S[])D[]-[]: 60 (36 inputs, 24 outputs) CP1E-NA20D[]-[]: 20 (12 inputs, 8 outputs)  | 
|||
| Built-in
 input func- tions  | 
High-
 speed counters  | 
High-speed
 counter mode/ maximum frequency  | 
Incremental Pulse Inputs
 10 kHz: 6 counters 5 counters (only for 10 I/O points) Up/Down Inputs 10 kHz: 2 counters Pulse + Direction Inputs 10 kHz: 2 counters Differential Phase Inputs (4x) 5 kHz: 2 counters  | 
Incremental Pulse Inputs
 100 kHz: 2 counters, 10 kHz: 4 counters Up/Down Inputs 100 kHz: 1 counters, 10 kHz: 1 counters Pulse + Direction Inputs 100 kHz: 2 counters Differential Phase Inputs (4x) 50 kHz: 1 counter, 5 kHz: 1 counter  | 
| Counting mode | Linear mode
 Ring mode  | 
|||
| Count value | 32 bits | |||
| Counter reset
 modes  | 
Phase Z and software reset (excluding increment pulse input)
 Software reset  | 
|||
| Control method | Target Matching
 Range Comparison  | 
|||
| Input interrupts | 6 inputs (4 inputs only for 10 I/O points)
 Interrupt input pulse width: 50 μs min.  | 
|||
| Quick-response Inputs | 6 inputs (4 inputs only for 10 I/O points)
 Input pulse width: 50 μs min.  | 
|||
| Normal
 input  | 
Input constants | Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms).
 Set values: 0, 1, 2, 4, 8, 16, or 32 ms  | 
||
| Built-in
 output func- tions  | 
Pulse
 outputs (Models with transistor outputs only)  | 
Pulse output
 method and output frequency  | 
Pulse output function not
 included  | 
Pulse + Direction Mode
 1 Hz to 100 kHz: 2 outputs  | 
| Output mode | Continuous mode (for speed control)
 Independent mode (for position control)  | 
|||
| Number of
 output pulses  | 
elative coordinates: 0000 0000 to 7FFF
 FFFF hex (0 to 2147483647) Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2147483647 to 2147483647)  | 
|||
| Acceleration/
 deceleration curves  | 
Trapezoidal acceleration and deceleration
 (Cannot perform S-curve acceleration and deceleration.)  | 
|||
| Changing SVs
 during instruction execution  | 
Only target position can be changed. | |||
| Origin searches | Included | |||
| Pulse
 outputs (Models with transistor outputs only)  | 
Frequency | PWM output function not
 included  | 
2.0 to 6,553.5 Hz (in increments of 0.1 Hz)
 with 1 output or 2 Hz to 32,000 Hz (in increments of 1 Hz) with 1 output  | 
|
| Duty factor | 0.0% to 100.0% (in increments of 0.1%)
 Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and +5%/-0% at 10,000 Hz to 32,000 kHz  | 
|||
| Output mode | Continuous Mode | |||
| Built-in analog | Analog input | Analog function not included | Setting range: 0 to 6,000 (2 channels only
 for NA-type)  | 
|
| Analog output | Setting range: 0 to 6,000 (1 channels only
 for NA-type)  | 
|||
| Analog adjusters | E/N/NA[][]-type: 2 adjusters (Setting range: 0 to 255)
 E/N[][]S(1)-type: None  | 
|||
| Com-
 muni- cations  | 
B-type Peripheral USB Port | Conforming to USB 2.0 B type connector | ||
| Transmission
 distance  | 
5 m max. | |||
| Built-in RS-232C port | No built-in RS-232C port | Interface: Conforms to EIA RS-232C. | ||
| Communications
 method  | 
Half duplex | |||
| synchronization | Start-stop | |||
| Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2
 kbps  | 
|||
| Transmission
 distance  | 
15 m max. | |||
| Supported
 protocol  | 
• Host Link
 • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master  | 
|||
| Built-in RS-485 port | No built-in RS-485 port | N30/40/60S1-type only
 Interface: Conforms to EIA RS-485. 2-wire sensors No isolation  | 
||
| Communications
 method  | 
Half duplex | |||
| synchronization | Start-stop | |||
| Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2
 kbps  | 
|||
| Transmission
 distance  | 
50 m max. | |||
| Supported
 protocol  | 
• Host Link
 • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master  | 
|||
| Serial Option port | Option Board cannot be
 mounted.  | 
N30/40/60 and NA20-type only
 1 port  | 
||
| Mountable
 Option Boards  | 
One RS-232C port: CP1W-CIF01
 One RS-422A/485 port (not isolated): CP1W-CIF11 One RS-422A/485 port (isolated): CP1W-CIF12-V1 One Ethernet port: CP1W-CIF41  | 
|||
| Communications
 method  | 
Depends on Option Board. | |||
| synchronization | Depends on Option Board. | |||
| Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2
 kbps  | 
|||
| Compatible
 protocols  | 
• Host Link
 • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master  | 
|||
| Number of tasks | 17
 • One cyclic execution task • One scheduled interrupt task (always interrupt task 1) • Six input interrupt tasks (interrupt tasks 2 to 7) • Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)  | 
|||
| Maximum subroutine number | 128 | |||
| Maximum jump number | 128 | |||
| Scheduled interrupt tasks | 1 interrupt task | |||
| Clock | Clock function not included.
 The time of error occurrence displays 01-01-01 01:01:01 Sunday  | 
Included.
 Accuracy (monthly deviation): -4.5 min to -0.5 min at ambient temperature of 55°C, -2.0 min to +2.0 min at ambient temperature of 25°C, -2.5 min to +1.5 min at ambient temperature of 0°C  | 
||
| Memory
 backup  | 
Built-in EEPROM | Ladder programs and parameters are automatically saved to built-in EEPROM
 A section of the Data Memory Area can be saved to the built-in EEPROM.  | 
||
| Battery backup With
 CP1W-BAT01 Battery (Sold separately)  | 
Battery cannot be mounted. | CP1W-BAT01 can be used.
 Maximum battery service life: 5 years Backup Time Guaranteed value (ambient temperature: 55°C): 13,000 hours (approx. 1.5 years) Effective value (ambient temperature: 25°C): 43,000 hours (approx. 5 years)  | 
||
| CIO
 Area  | 
Input Bits | 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99) | ||
| Output Bits | 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199) | |||
| Serial PLC Link Words | 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289) | |||
| Work Area (W) | 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99) | |||
| Holding Area (H) | 800 bits (50 words): H0.00 to H49.15 (H0 to H49)
 Bits in this area maintain their ON/OFF status when operating mode is changed.  | 
|||
| Auxiliary Area (A) | Read-only: 7,168 bits (448 words) A0 to A447
 Read/write: 4,896 bits (306 words) in words A448 to A753  | 
|||
| Temporary Relay Area (TR) (TR Area) | 16 bits: TR0 to TR15 | |||
| Timer Area (T) | 256 timer numbers (T0 to T255 (separate from counters)) | |||
| Counter Area (C) | 256 counter numbers (C0 to C255 (separate from timers)) | |||
| Data Memory Area (D) | 2 Kwords: D0 to D2047
 Of these, 1,500 words can be saved to the backup memory (built-in EEPROM) using settings in the Auxiliary Area.  | 
8 Kwords: D0 to D8191
 Of these, 7,000 words can be saved to the backup memory (built-in EEP-ROM) using settings in the Auxiliary Area  | 
||
| Operating modes | PROGRAM mode:
 Program execution is stopped. Preparations can be executed prior to program execution in this mode. MONITOR mode: Programs are executed. Some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode. RUN mode: Programs are executed. This is the normal operating mode.  | 
|||
last update: February 1, 2023