Page top

Industrial Automation

Industrial Automation

Discontinued On Mar. 2024

GRT1 Series

SmartSlice CompoNet Communications Unit

GRT1 Series

The CompoNet-compliant unit can interface up to 256 inputs and 256 outputs at one node.

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Specifications

Model GRT1-CRT
Network power supply voltage 14 to 26.4 V DC
Unit power supply voltage 20.4 to 26.4 V DC (24 V +10%/-15%)
I/O power supply voltage 20.4 to 26.4 V DC * (24 V +10%/-15%)
Noise immunity Conforms to IEC 61000-4-4, 2 kV (power line)
Vibration resistance+ 10 to 60 Hz, 0.7-mm double amplitude
60 to 150 Hz: 50 m/s2
Shock resistance 150 m/s2
Dielectric strength 500 V AC between isolated circuits
Insulation resistance 20 MΩ min. between isolated circuits
Ambient operating temperature -10 to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Ambient operating environment No corrosive gases
Ambient storage temperature -25 to 65°C (with no icing or condensation)
Mounting method 35-mm DIN track mounting

* For power supply input to the Slice I/O Units.

Specifications of the CompoNet Communications Unit

Item Specification
I/O points Inputs: 32 bytes maximum (including status and areas which the Unit does not use)
Output: 32 bytes maximum (including areas which the Unit does not use)
Maximum number of SmartSlice I/O
Units
64 (Do not count the End Unit.)
Status area 1 word (This word shows the status of the CompoNet Communications Unit.)
Parameter backup and restore You can back up or restore a maximum of 2 KB of data for one CompoNet Communications Unit.
Baud rate The CompoNet Communications Unit uses the baud rate of the CompoNet Master Unit
(93. 75 kbps, 1.5 Mbps, 3 Mbps, or 4 Mbps).
Communications media You can use these cables:
Round Cable I (JIS C 3306, VCTF 2-core 0.75-mm2 twisted-pair cable)
Round Cable II (JIS C 3306, VCTF 4-core 0.75-mm2 twisted-pair cable)
Flat Cable I (without sheath, DCA4-4F10)
Note: The Round Cable I, Round Cable II and Flat Cable I are different types of cable. You must
use a Repeater to divide a branch line from the main line to use more than one type of cable.
Indicators MS (green/red): This indicator shows the status of the CompoNet Communications Unit.
NS (green/red): This indicator shows the communications status of the CompoNet network.
TS (green/red): This indicator shows the status of the SmartSlice I/O Terminal.
UNIT PWR (green): This indicator shows the status of the Unit power supply.
I/O PWR (green): This indicator shows the status of the I/O power supply.
Switches Rotary switches: There are two rotary switches. You use them to set the node address.
DIP switch: There is one DIP switch with four pins. You use them to set the operating mode.
Connectors There is one CompoNet communications connector.
Terminals Clamp terminals for Unit power supply (24 VDC)
Clamp terminals for I/O power supply (24 VDC)
Power consumption 2.5 W
Power consumption for each
SmartSlice I/O Terminal block
80 W max.
(You must divide the I/O Terminal into blocks to use more than 80 W.)
SmartSlice I/O Terminal blocks Main block and a maximum of two expansion blocks
Current consumption for I/O power
supply
4 A max.
Weight 137 g
Accessories None